; must be
fire-proof; must have doors opening outwards; and the vent-pipes must
terminate at a safe place in the open. Apparatus of group (_b_) must
not be placed in a dwelling-room and only in an adjoining room if the
gasholder is of less than 600 litres capacity. Apparatus of group
(_c_) must be in an independent building which must be at least 33
feet from occupied premises if the capacity of the gasholder is 6000
litres and upwards. Half this distance suffices for gasholders containing
600 to 6000 litres. These distances may be reduced at the discretion of
the local authorities provided a substantial partition wall at least 1
foot thick is erected. Apparatus of group (_d_) must be at least 50
feet from occupied premises and the gasholder and generator must not be
in the same building.
The fourth section deals with the question of authorisation for the
installation of acetylene plant. Apparatus of group (_a_) may be
installed without obtaining permission from any authorities. In regard to
apparatus of the other groups, permission for installation must be
obtained from local or other authorities.
The fifth section relates to the working of acetylene plant.